Skip to main content

US32-SM (Retired)

StrongMesh™ Wireless Communicating Thermostat

Replacement Product X5N-SM

    Features
    • Controls Conventional Gas/Electric Systems with up to 2 Heat and 2 Cool Stages
    • Controls Heat Pump Systems with up to 3 Heat and 2 Cool Stages
    • Vibrant Blue Backlight with Selectable Brightness
    • Automatic Changeover from Heat-to-Cool and Cool-to-Heat
    • 2 Occupied (Day-Cool & Day-Heat) and 2 Unoccupied (Night-Cool & Night-Heat) Setpoints
    • Selectable Fahrenheit or Celsius Display
    • Commercial Lockout with Programmable Override Timer, and +/-3F or +/-5F Temp Adjustment
    • Setback Terminal Input with Selectable Occ/Unocc Operation or Mode OFF
    • Lockable Access Cover
    • Plenum Fan Switch
    • HVAC equipment control using dry contact relays
    • 2 LED lights; LEDs triggered via 2 Digital Inputs which can be used for Equipment Faults, Dirty Filters, Condensate Overflow, or any other contact closure input
    • Up to 6 Remote Indoor Sensors (NT-TEMP or NT-IDS) and 1 Outdoor Sensor (NT-TEMP + NT-OUTDOOR probe)
    • Optional Occupancy Sensors Available (Ceiling and Wall Mount)
    • Integrated NetX™ API language, Allowing for the Development of 3rd Party Apps

    Rated Voltage: 20V to 30VAC, 24VAC nominal
    Rated A.C. Current: 0.05 to 0.75 Amp continuous, per output, surges to 3 Amps max.
    Rated D.C. Current: 0.05 to 0.75 Amp continuous, per output, surges to 3 Amps max.
    Control Range: Heating: 38 to 88°F in 1° steps (6 to 30°C in 1° steps)
                                  Cooling: 60 to 108°F in 1° steps (16 to 40°C in 1° steps)
    Sensing Range: 20 to 124°F (0 to 48°C)
    Control Accuracy: +/-1°F @ 68°F (0.5°C @ 20°C)
    Minimum Heat/Cool Deadband: 2°F (1°C)
    Dimensions: 4.5”H x 4”W x 1”D (114mm x 102mm x 26mm)
    Thermostat LEDs: LED1 - Red, LED2 -Red
    Equipment Terminations: R-24V switching voltage,  W1 - Heat1, W2 - Heat2, G - Fan, Y1 - Cool1, Y2 - Cool2
    Power Terminations: 24V - isolated remote power, 24V(c) - power common (from HVAC equipment or remote power)
    Thermostat Communications:  StrongMesh™ wireless communications

    2-Heat/2-Cool for Conventional Gas, Electric, Oil, and Radiant Heat HVAC Systems
    3-Heat/2-Cool for Heat Pump HVAC Systems with Normal or Dual Fuel Applications
    Setback Thermostat with Wireless StrongMesh™ Communications
    Secure Direct Connection via any NetX Network Controller

    The US32-SM communicating setback thermostat is our 5th Generation version with a beautiful new blue backlight and a secondary display for remote sensors. It's designed for new and replacement commercial or residential applications for both conventional Gas/Electric and Heat Pump HVAC equipment. Using the NetX™ network controller connected to a WCM-2 StrongMesh™ Wireless Coordinator and the NetX™ Command Center software for XBus™ and StrongMesh™ thermostats, NetX™ makes it simple with near effortless changes to each setting on the thermostat. The pushbuttons on the thermostat can be locked to give restricted override capabilities, and the optional Occupancy Sensor enables automatic energy savings.

     

    Accessories