Skip to main content

NT-TEMP

Remote Temperature Sensor (connects directly to thermostat)

  • Advanced Remote Sensors
  • Use with UP32 thermostat
  • Advanced sensor network allows up to 11 remote sensors on each UP32
  • Simple 3-Wire Daisy Chain Connection

    Rated Voltage: 
    20V to 30VAC, 24VAC nominal

    Internal Temp Sensor Range: 
    +28°F to 119°F in 1° steps (-2°C to 48°C in 1° steps)

    External Temp Sensor Range:  
    Outdoor:  -54 to +119°F (-48 to +48°C)      
    AUX1, 2, & 3: -40 to +200°F (-40 to +48°C)

    Measurement Accuracy: 
    ± 1°F (0.5°C)

    Terminations: 
    RS1 - Data, RS+V – Power, RS2 – Return, 1 & 2 – External Temp Sensor Leads

    Sensor Type
    Remote Sensor
    • Up to Eleven (11), Sensors Can Be Connected to a Single UP32 Thermostat
    • Six (6) of the Eleven (11) Sensors Can Be Used as INDOOR Sensors For Automatic Room Temperature Averaging 

    Sensor Types, per thermostat, Include:

    • INDOOR – up to 6 with automatic averaging (use Internal Sensor or NT-FS probe)
    • OUTDOOR – qty 1 (use NT-OUTDOOR probe)
    • AUX1 – qty 1 (use NT-PROBE)
    • AUX2 – qty 1 (use NT-PROBE)
    • AUX3 – qty 1 (use NT-PROBE or NT-H20)

    Measurement Ranges with Sensor Types:

    • INDOOR   +28°F to +119°F (-2°C to +48°C)
    • OUTDOOR  -54°F to +119°F (-48°C to +48°C)
    • AUX1 -40°F to +200°F (-40°C to +48°C)
    • AUX2 -40°F to +200°F (-40°C to +48°C)
    • AUX3 -40°F to +200°F (-40°C to +48°C)
    • WATER PROBE:  -40°F to +200°F (-40°C to +48°C)
    • HUMIDITY 0 to 100% Non-Condensing
    • By Way of the UP32 Thermostat, Email & Text Message Alerting for up to 4 Recipients; Alerts include High/Low Temperatures for Indoor, Outdoor, and 3 Aux Temp Sensors
    • Simple 3-Wire Communications Bus (using standard CAT5 Cable)
    • Up to 300ft (90m) of Cabling Can Be Used
    • Selectable Fahrenheit or Celsius Display on UP32 Thermostat

    The NetworkThermostat NT-TEMP and NT-HUM remote sensors are designed to sense air temperature (NT-TEMP) and/or humidity (NT-HUM) at locations remote to the UP32. There are five (5) individual sensor temperature sensor types plus one (1) humidity sensor with two options. One of each type of sensor can be used on the UP32, plus a total of up to six (6) remote INDOOR sensors to provide automatic averaging for the space temperature. The sensors are designed for attaching to a vertically mounted single-gang low-voltage box.  DIP switch configuration on the NT-TEMP allows it to be used as an indoor room sensor (using the integrated temp sensor), or to be used as an outdoor sensor (with the addition of the NT-OUTDOOR probe), or any of up to 6 auxiliary sensors, Aux1-Aux6, by adding the NT-PROBE stainless steel probe and integrated single-gang box, or the NT-H2O for direct water temperature sensing.

    Sensing applications can include HVAC control (Indoor and Outdoor sensing) and general monitoring and/or alerting, such as Supply Air, Return Air, Humidity, Walk-In Freezers, Refrigerated Display Cases, Computer Rooms, Wine Rooms, Water Temp, and countless other applications.