Ethernet Programmable Thermostat
Replaced by → NetX X5-IP
Features
- Integrated Web Browser with 10/100Mbps Ethernet Communications
- PC, Mac, Tablet & Smart Phone Connectivity
- Automatic Heat <-> Cool Changeover
- 7-Day Programmable, with up to Four (4) Schedules per Day
- Selectable Smart Schedule Recovery™ allows system to achieve desired setpoint at the beginning of the schedule
- Vacation Scheduling, including Start Now and Start Later Functions
- Fahrenheit or Celsius Display
- Programmable Fan, with Auto, On and Recirculation Functions
- Integrated Weatherbug Forecasts and Current Conditions
- Weatherbug® Outdoor Temperature (allows Heat Pump balance point use without the need for a real remote sensor)
- Keyboard Lockout Feature for commercial applications, includes adjustable override from 0 hrs to 8 hrs
- Selectable +/- 3 Degrees F or +/- 5 Degrees F adjustment during override
- Dual Email & Text Message Alerting Features for User and Service Contractor (total of up to 4 recipients for each alert!)
- Random Restart on Power Up™ Randomly Staggers restart of HVAC System After a Power Outage to Minimize Peak In-Rush Current for a Facility
- Efficient Equipment Restart™ Randomizes Equipment Starts to Minimize Multiple Units Turning on Simultaneously When There Are Several RP32 or UP32 Thermostats at the Location
Specs
Rated Voltage: 20V to 30VAC, 24VAC nominal
Rated A.C. Current: 0.05 to 0.75 Amp continuous, per output, surges to 3 Amps max.
Rated D.C. Current: 0.05 to 0.75 Amp continuous, per output, surges to 3 Amps max.
Control Range: Heating: 38 to 88°F in 1° steps (6 to 30°C in 1° steps) Cooling: 60 to 108°F in 1° steps (16 to 40°C in 1° steps)
Sensing Range: 20 to 124°F (0 to 48°C)
Control Accuracy: +/-1°F @ 68°F (0.5°C @ 20°C)
Minimum Heat/Cool Deadband: 2°F (1°C)
Communications: Ethernet 10/100Mbps with RJ45 Ethernet dongle
Dimensions: 4.5”H x 4”W x 1”D (114mm x 102mm x 26mm)
Thermostat LEDs: Red – Emergency Heat, Yellow – Inefficient Equipment Run, Green – Change Filter
Equipment Terminations: R-24V switching voltage, W1-Heat1 or aux/emer Heat, G-Fan, Y1-Compressor1, Y2-Compressor2, O/W2- Heat2 or Rev. Valve in Cooling, B-Rev. Valve in Heating
Power Terminations: 24V-remote power (not used), 24V(c)-power common (from HVAC equipment)
Description
2-Heat/2-Cool for Conventional Gas, Electric, Oil, and Radiant HVAC systems
3-Heat/2-Cool for Heat Pump HVAC systems, including Dual Fuel systems
Integrated Web Server with Email/Text Message Alerting
Proudly Made in the USA. The RP32-IP thermostat is a programmable communicating thermostat with connectivity utilizing 10/100Mbps Ethernet technology. In conventional mode, this Ethernet thermostat will work for the vast majority of the HVAC units in the marketplace. In conventional mode, the unit can control up to two (2) stages of air conditioning and up to two (2) stages of heating. In heat pump mode, the thermostat can control up to two (2) stages of air conditioning and up to three (3) stages of heat, including auxiliary heat and emergency heat, with electric or gas (dual fuel). Integrated Weatherbug gives full 7-day forecasting and heat pump balance point control without the need for an outdoor sensor. The unit will work for the vast majority of the HVAC units in the marketplace.
The RP32-IP ethernet thermostat with an embedded web server is a great solution where scheduling is needed in the thermostat (programmable) without the need for remote sensing.