Rated Voltage:
20V to 30VAC, 24VAC nominal, or 24VDC with jumper removed on faceplate
Rated A.C. / D.C. Current:
0.05 to 0.75 AC / 0.0 to 0.75 DC Amp continuous, per output, surges to 3 Amps maximum
Thermostat Sensing Range:
32˚F to 124°F (0˚C to 48°C)
Control Accuracy: ±1°F @ 68°F (±0.5°C @ 20°C)
Temperature Control Range:
- Heating: 38 to 88°F (6 to 30°C) in 1° steps
- Cooling: 60 to 108°F (16 to 40°C) in 1° steps
Minimum Deadband:
2°F (1°C)
Humidity Sensing Range:
0% to 100% Relative Humidity
- Accuracy: ±3% from 10% - 90%
Humidity Control Range:
- Humidify: 10% to 60% in 5% steps
- Dehumidify: 35% to 75% in 5% steps
Dimensions:
5.1”H x 4.7”W x 1.15”D (128mm x 119mm x 29mm)
Equipment Terminations:
R - 24VAC switching voltage from HVAC Equipment
W1 - Heat1 or Aux/Emer Heat
G - Fan, Y1-Compressor1
Y2 - Compressor2
O/W2 - Heat2 or Rev. Valve in Cooling
B - Rev. Valve in Heating
Aux Relay Terminations:
K/H/D – Humidify / Dehumidify / Relay Schedule (KHD or K2) / Damper / IAQ
K2 – Relay Schedule (KHD or K2) / Damper / IAQ
Power Terminations:
R - 24VAC switching voltage from HVAC Equipment
24V - Separate Power (24VAC/DC), requires faceplate jumper removal
24V(c) - power return
Input Terminations:
LED1 (Filter Icon Selectable), LED2 (Fault Icon Selectable), CLK1 ( + ), CLK2 ( - ) (Occupancy)
Remote Sensor Terminations:
RS+V - Power, RS2 - Return, RS1 - Data
Wireless Radio:
2.4GHz 802.11b/g, Security: Open, WEP, WPA-PSK, WPA2-PSK
Ethernet:
10/100Mbps, 802.3, Auto-Negotiation, Auto-MDIX
Accessory Port:
SIM port for NetX CO2/VOC Sensor
Protocols:
http, native NetX API, BACnet-IP and Modbus TCP/IP over Wi-Fi